Wisconsin Code § 101.14

Fire inspections, prevention, detection and suppression
Open in Lexace · Ask the AI about this section
(1) (a) The department may make reasonable
orders for the repair or removal of any building or other structure
which for want of repair or by reason of age or dilapidated condition or for any other cause is especially liable to fire, and which is
so situated as to endanger other buildings or property and for the
repair or removal of any combustible or explosive material or inflammable conditions, dangerous to the safety of any building or
premises or the occupants thereof or endangering or hindering
fire fighters in case of fire.
(am) Notwithstanding par. (a), the department may not require the owner or operator of a mobile kitchen to install or maintain an automatic fire suppression system or an exhaust hood in,
or as part of, the mobile kitchen if all of the following apply:
1. The mobile kitchen is less than 365 square feet in size.
2. The mobile kitchen is used on fewer than 12 days a year
for the purpose of cooking.
(b) The secretary and any deputy may at all reasonable hours
enter into and upon all buildings, premises and public thoroughfares excepting only the interior of private dwellings, for the purpose of ascertaining and causing to be corrected any condition liable to cause fire, or any violation of any law or order relating to
the fire hazard or to the prevention of fire.
(bm) The secretary and any deputy may, at all reasonable
hours, enter the interior of private dwellings at the request of the
owner or renter for the purpose of s. 101.145 (6) or 101.645 (4).
(c) The department is hereby empowered and directed to provide the form of a course of study in fire prevention for use in the
public schools, dealing with the protection of lives and property
against loss or damage as a result of preventable fires, and transmit the same by the first day of August in each year to the state superintendent of public instruction.
(2) (a) The chief of the fire department in every city, village
or town, except cities of the 1st class, is constituted a deputy of
the department, subject to the right of the department to relieve
any such chief from duties as such deputy for cause, and upon
such suspension to appoint some other person to perform the duty
imposed upon such deputy. The department may appoint either
the chief of the fire department or the building inspector as its
deputy in cities of the 1st class.
(b) The chief of every fire department shall provide for the inspection of every public building and place of employment to determine and cause to be eliminated any fire hazard or any violation of any law relating to fire hazards or to the prevention of
fires. For purposes of this paragraph, the seasonal placement of a
Christmas tree in the rotunda of the state capitol building or in a
church is presumed not to be a fire hazard.
(c) 1. Except as provided under subd. 2., the chief of every
fire department shall provide that the inspections required under
par. (b) be made at least once in each nonoverlapping 6-month period per calendar year in all of the territory served by his or her
fire department. The chief of a fire department may require more
frequent inspections than required under this subdivision. The
department by rule shall provide for general exceptions, based on
the type of occupancy or use of the premises, where less frequent
inspections are required. Upon written request by the chief of a
fire department, the department by special order may grant an exception to a city, village or town to conduct less frequent inspections than required under this subdivision.
2. In 1st class cities, the fire chief may establish the schedule
of fire inspections in that city. The fire chief shall base the frequency of the inspections on hazardous classification, the proportion of public area, the record of fire code violations, the ratio of
occupancy to size and any other factor the chief deems significant. Property other than residential property with 4 dwelling
units or less shall be inspected at least once annually.
(cm) In addition to the requirements of pars. (b) and (c), a fire
department shall provide public fire education services.
(d) The chief of every fire department, or, in 1st class cities,
the building inspector appointed by the department under par. (a),
shall designate a sufficient number of inspectors to make the inspections required under pars. (b) and (c).
(e) Written reports of inspection shall be made and kept on
file by the authority having jurisdiction to conduct inspections, or
its designee, in the manner and form required by the department.
(f) Every inspection required under pars. (b) and (c) is subject
to the supervision and direction of the department, which shall,
after audit, certify to the commissioner of insurance after the expiration of each calendar year each city, village or town where the
inspections for the year have been made, and where records have
been made and kept on file as required under par. (e).
(3) The department shall annually conduct training sessions
and provide manuals and other materials and services to assist
deputies and inspectors in the fulfillment of their duties under
sub. (2).
(4) (a) The department shall make rules, pursuant to ch. 227,
requiring owners of places of employment and public buildings to
install such fire detection, prevention or suppression devices as
will protect the health, welfare and safety of all employers, employees and frequenters of places of employment and public
buildings.
(b) 1m. In this paragraph, “private student residential building” means a privately owned and operated residential building
that has a capacity of at least 100 occupants, that is occupied by
persons at least 80 percent of whom are enrolled in an institution
of higher education, and that has attributes usually associated
with a student residence hall or dormitory such as a food service
plan or occupancy by a resident advisor.
1r. Except as provided in subds. 2. and 3., the rules of the department shall require all such places and buildings over 60 feet
in height, the construction of which is begun after July 3, 1974, to
contain an automatic fire sprinkler system on each floor.
2. a. Subdivision 1r. does not apply to any open parking
structure, as defined by the department.
b. If the department determines that water would cause irreparable damage and undue economic loss if discharged in such
places or buildings, it shall require a suppression device which
has a substance other than water.
c. Except as provided in subd. 3., subd. 1r. does not apply to
any building over 60 feet in height the construction of which is
completed or is begun prior to July 3, 1974.
3. The rules of the department shall require all of the
following:
a. Every residence hall and dormitory over 60 feet in height,
the initial construction of which was begun before
April 26, 2000, that is owned or operated by the board of regents
of the University of Wisconsin System to contain an automatic
fire sprinkler system on each floor by January 1, 2006.
b. Every residence hall and dormitory, the initial construction of which is begun on or after April 26, 2000, that is owned or
operated by the board of regents of the University of Wisconsin

System to have an automatic fire sprinkler system installed on
each floor at the time the residence hall or dormitory is
constructed.
c. Every residence hall and dormitory over 60 feet in height,
the initial construction of which was begun before January 7,
2006, that is owned or operated by an institution of higher education, other than a residence hall or dormitory that is owned or operated by the Board of Regents of the University of Wisconsin
System, to contain an automatic fire sprinkler system on each
floor by January 1, 2014.
d. Every residence hall and dormitory, the initial construction of which is begun on or after January 7, 2006, that is owned
or operated by an institution of higher education, other than a residence hall or dormitory that is owned or operated by the Board
of Regents of the University of Wisconsin System, to have an automatic fire sprinkler system installed on each floor at the time
the residence hall or dormitory is constructed.
e. Every student residential facility operated by a fraternity,
sorority, or other organization authorized or sponsored by an institution of higher education, the initial construction of which
was begun before January 7, 2006, and every private student residential building over 60 feet in height, the initial construction of
which was begun before January 7, 2006, to contain an automatic
fire sprinkler system on each floor by January 1, 2014.
f. Every student residential facility operated by a fraternity,
sorority, or other organization authorized or sponsored by an institution of higher education, the initial construction of which is
begun on or after January 7, 2006, and every private student residential building, the initial construction of which is begun on or
after January 7, 2006, to have an automatic fire sprinkler system
installed on each floor at the time the facility is constructed.
(c) The rules of the department governing such places and
buildings under 60 feet in height shall be based upon but may
vary from those provisions in the International Code Council,
Inc., building code which relate to fire detection, prevention and
suppression in public buildings and places of employment.
(d) To the extent that the historic building code applies to the
subject matter of this subsection, each qualified historic building,
as defined under s. 101.121 (2) (c), is exempt from this subsection if the owner elects to be subject to s. 101.121.
(de) 1. Notwithstanding par. (a) and sub. (1) (a) and s. 101.02
(15) (j), the department may not require, and notwithstanding s.
101.02 (7) (a) and (7r), no city, village, or town may enact or enforce an ordinance that requires, a county or organized agricultural society, association, or board to install or maintain an automatic fire suppression system in, or as part of, a building on fairgrounds if all of the following are satisfied:
a. The building is open to the public only for seasonal or
temporary event use for 180 cumulative days or fewer per year.
b. Public access to the building is provided by garage style
doors that remain open when the building is open to the public.
2. Notwithstanding s. 101.02 (7) (a) and (7r), if a city, village, or town has in effect on March 3, 2016, an ordinance with a
requirement that is inconsistent with subd. 1., the requirement
does not apply and may not be enforced.
(dm) Each building required by rule under this subsection to
contain fire detection, prevention and suppression devices shall
have the necessary devices installed at the time of its
construction.
(e) Whoever violates this subsection may be fined not less
than $100 but not more than $500 for each day of violation.
(f) The department may inspect all buildings covered by this
subsection and may issue such orders as may be necessary to assure compliance with it.
(g) As used in this subsection:
1. “Automatic fire sprinkler system” has the meaning provided in s. 145.01 (2).
2. “Fire detection, prevention and suppression devices” include but are not limited to manual fire alarm systems, smoke and
heat detection devices, fire extinguishers, standpipes, automatic
fire suppression systems and automatic fire sprinkler systems.
(4m) (a) In this subsection:
1. “Automatic fire sprinkler system” has the meaning given
in s. 145.01 (2).
2. “Dwelling unit” has the meaning given in s. 101.61 (1).
4. “Nondwelling unit portions” means the common use areas
of a multifamily dwelling, including corridors, stairways, basements, cellars, vestibules, atriums, community rooms, laundry
rooms or swimming pool rooms.
5. “Political subdivision” means a county, city, village or
town.
5m. “Two-hour fire resistance” means 2-hour fire separations for all walls that separate dwelling units, exit corridors and
exit stair enclosures and for all floors and ceilings, so that the
specified walls, floors and ceilings are capable of resisting fire for
a period not shorter than 2 hours.
(am) A political subdivision may enact ordinances, as provided in this paragraph, that require an automatic fire sprinkler
system or 2-hour fire resistance in every multifamily dwelling.
Any ordinance enacted under this paragraph shall meet the standards established under pars. (b) and (c) or under pars. (d) and
(e).
(b) The department shall require an automatic fire sprinkler
system or 2-hour fire resistance in every multifamily dwelling
that contains any of the following:
1. Total floor area, for all individual dwelling units, exceeding 16,000 square feet.
2. More than 20 dwelling units.
3. Total floor area of its nondwelling unit portions exceeding
the limits established in par. (c).
(c) An automatic fire sprinkler system or 2-hour fire resistance is required under par. (b) in a multifamily dwelling constructed by any of the following types of construction if the total
floor area of the nondwelling unit portions in the multifamily
dwelling exceeds the following:
1. Type 1 fire resistive construction, 16,000 square feet.
2. Type 2 fire resistive construction, 12,000 square feet.
3. Type 3 metal frame protected construction, 8,000 square
feet.
4. Type 4 heavy timber construction, 5,600 square feet.
5. Type 5A exterior masonry protected, 5,600 square feet.
6. Type 5B exterior masonry unprotected, 5,600 square feet.
7. Type 6 metal frame unprotected, 5,600 square feet.
8. Type 7 wood frame protected construction, 5,600 square
feet.
9. Type 8 wood frame unprotected construction, 4,800
square feet.
(d) A political subdivision’s ordinances, enacted to meet the
requirements of this paragraph and par. (e), shall require an automatic fire sprinkler system or 2-hour fire resistance in every multifamily dwelling that contains any of the following:
1. Total floor area, for all individual dwelling units, exceeding 8,000 square feet.
2. More than 8 dwelling units.
3. Total floor area of its nondwelling unit portions exceeding
the limits established in par. (e).

(e) A political subdivision’s ordinances, enacted to meet the
standards established in par. (d) and this paragraph, shall require
an automatic fire sprinkler system or 2-hour fire resistance in every multifamily dwelling that is constructed by any of the following types of construction if the total floor area of the nondwelling
unit portions in the multifamily dwelling exceeds the following:
1. Type 1 fire resistive construction, 12,000 square feet.
2. Type 2 fire resistive construction, 10,000 square feet.
3. Type 3 metal frame protected construction, 8,000 square
feet.
4. Type 4 heavy timber construction, 5,600 square feet.
5. Type 5A exterior masonry protected, 5,600 square feet.
6. Type 5B exterior masonry unprotected, 5,600 square feet.
7. Type 6 metal frame unprotected, 5,600 square feet.
8. Type 7 wood frame protected construction, 5,600 square
feet.
9. Type 8 wood frame unprotected construction, 4,800
square feet.
(4r) (a) In this subsection, “fire detection, prevention, and
suppression devices” has the meaning given in sub. (4) (g) 2.
(b) A person may perform inspections of fire detection, prevention, and suppression devices being installed during the construction or alteration of, or the addition to, public buildings and
places of employment only if he or she has received certification
as an inspector from the department.
(c) 1. The department shall promulgate rules establishing
procedures and requirements for issuing certifications for purposes of par. (b). The department shall include in the rules a requirement that the person hold a valid certification from the national fire protection association qualifying him or her as a certified fire inspector I or that he or she hold a valid equivalent
certification.
2. The department shall determine which certifications issued by other entities will qualify as valid equivalent certifications. Notwithstanding s. 227.10 (1), determinations under this
subdivision shall not be promulgated as rules.
(d) The department shall provide assistance to any nationwide
or statewide organization that represents fire chiefs and that is engaged in providing training and certification opportunities for
persons seeking to receive certification by the department under
this subsection.

‹ Prev All Wisconsin sections Next ›


Lexace provides legal information, not legal advice, and no attorney–client relationship is created. Statute text is provided for general information and may not reflect the most recent amendments; verify against the official state code.