Utah Code § 15A-5-206

Amendments and additions to IFC related to hazardous materials, explosives,
Open in Lexace · Ask the AI about this section
fireworks, and flammable and combustible liquids.
(1) For IFC, Hazardous Materials - General Provisions, Chapter 50, Table 5003.1.1(1), Maximum
Allowable Quantity per Control Area of Hazardous Materials Posing a Physical Hazard, apply
footnote d to Explosives, Storage, Solid Pounds.
(2) IFC, Explosives and Fireworks, IFC, Chapter 56, Section 5601.1.3, Fireworks, Exception 4
is amended to add the following sentence at the end of the exception: "The use of fireworks
for display and retail sales is allowed as set forth in Utah Code, Title 53, Chapter 7, Utah Fire
Prevention and Safety Act, Sections 53-7-220 through 53-7-225; Utah Code, Title 11, Chapter
3, County and Municipal Fireworks Act; Utah Administrative Code, R710-2; and the State Fire
Code."
(3) For IFC, Chapter 57, Flammable and Combustible Liquids:
(a) IFC, Chapter 57, Section 5701.4, Permits, is amended to add the following at the end of the
section: "The owner of an underground tank that is out of service for longer than one year
shall receive a Temporary Closure Notice from the Department of Environmental Quality, and
a copy shall be given to the AHJ."
(b) IFC, Chapter 57, Section 5706.1, General, is amended to add the following special operation:
"8. Sites approved by the AHJ".
(c) IFC, Chapter 57, Section 5706.2, Storage and dispensing of flammable and combustible
liquids on farms and construction sites, is amended to add the following: On line five, after the
words "borrow pits", add the words "and sites approved by the AHJ".
(4) For IFC, Chapter 61, Liquefied Petroleum Gas:
(a) IFC, Chapter 61, Section 6101.2, Permits, is amended as follows: On line two, after the word
"105.6", add "and the adopted LP Gas rules".
(b) IFC, Chapter 61, Section 6103.1, General, is deleted and rewritten as follows: "General. LP
Gas equipment shall be installed in accordance with NFPA 54, NFPA 58, the adopted LP Gas
rules, and the International Fuel Gas Code, except as otherwise provided in this chapter."
(c) IFC, Chapter 61, Section 6104.3, Location of LP-Gas Containers, Table 6104.3, Location
of LP-Gas Containers, amends column heading "Minimum Separation Between LP-Gas
Containers and Buildings, Public Ways or Lot Lines of Adjoining Property" and footnote "g" by
deleting and replacing with the following: "Minimum separation between LP-Gas containers
and buildings, or lot lines of adjoining property that can be built on."
(d) Chapter 61, Section 6109.12, Location of storage outside of buildings, is amended as follows:
In Table 6109.12, Doorway or opening to a building with two or more means of egress, with
regard to quantities 720 or less and 721 -- 2,500, the currently stated "5" is deleted and
replaced with "10".
(e) IFC, Chapter 61, Section 6109.15.1, Automated cylinder exchange stations, is amended as
follows: Item # 4 is deleted and replaced with the following: "Item #4 Electrical equipment
inside of a cabinet storing cylinders, including but not limited to electronics associated with
vending operations, shall comply with requirements for Class I, Division 2, equipment in
accordance with NFPA 70."

(f) IFC, Chapter 61, Section 6110.1, Removed from service, is amended as follows: On line two,
after the word "discontinued", add the words "for more than one year or longer as allowed by
the AHJ,".
(g) IFC, Chapter 61, Section 6110.2, Removal from site is deleted.