Utah Code § 15A-4-303

Amendments to IPC applicable to South Jordan
Open in Lexace · Ask the AI about this section
The following amendments are adopted as amendments to the IPC for South Jordan:
(1) IPC, Section 312.10.2, is deleted and replaced with the following: "312.10.2 Testing. Reduced
pressure principle backflow preventer assemblies, double check-valve assemblies, pressure
vacuum breaker assemblies, reduced pressure detector fire protection backflow prevention
assemblies, double check detector fire protection backflow prevention assemblies, hose
connection backflow preventers, and spill-proof vacuum breakers shall be tested at the time of
installation, immediately after repairs or relocation and at least annually. The testing procedure
shall be performed in accordance with one of the following standards: ASSE 5013, ASSE
5015, ASSE 5020, ASSE 5047, ASSE 5048, ASSE 5052, ASSE 5056, CSA-B64.10, or CSA-
B64.10.1. Assemblies, other than the reduced pressure principle assembly, protecting lawn
irrigation systems that fail the annual test shall be replaced with a reduced pressure principle
assembly."

(2) IPC, Section 608.16.5, is deleted and replaced with the following: "608.16.5 Connections to
lawn irrigation systems. The potable water supply to lawn irrigation systems shall be protected
against backflow by a reduced pressure principle backflow preventer."