Utah Code § 15A-3-601

General provisions
Open in Lexace · Ask the AI about this section
The following are adopted as amendments to the NEC to be applicable statewide:
(1) The IRC provisions are adopted as the residential electrical standards applicable to residential
installations under the IRC. All other installations shall comply with the adopted NEC.
(2) In NEC, Section 210.8(A), the words "through 250-volt" are deleted.
(3) In NEC, Section 210.8(A) number (5), the word "Basements" is deleted and replaced with the
following:
"Unfinished portions or areas of the basement not intended as habitable rooms."
(4) In NEC, Section 210.8(A), number (6), the following is added after the word "Kitchens":
"where the receptacles are installed to serve the countertop surfaces."
(5) In NEC, Section 210.8(A), number (7) is deleted.
(6) In NEC, Section 210.8(D), numbers (8) through (12) are deleted.
(7) NEC, Section 210.8(F), is deleted.
(8) NEC, Sections 210.52(C) number (2) and number (3) are deleted and replaced with the
following:
 "210.52(C)(2) Island and peninsular countertops and Work Surfaces. Receptacle outlets,
if installed to serve an island or peninsular countertop or work surface, shall be installed in
accordance with 210.52(C)(3). If a receptacle outlet is not provided to serve an island or
peninsular countertop or work surface, provisions shall be provided at the island or peninsula
for future addition of a receptacle outlet to serve the island or peninsular countertop or work
surface.
 210.2(C)(3) Receptacle outlet location. Receptacle outlets shall be located in one or
more of the following:
(a) On or above, but not more than 500 mm (20 inches) above a countertop or work surface.

(b) In a countertop using receptacle assemblies listed for use in countertops.
(c) In a work surface using receptacle outlet assemblies listed for use in work surfaces or listed
for use in countertops.
 Receptacle outlets rendered not readily accessible by appliances fastened in place,
appliance garages, sinks, or range tops as covered in the exception to 210.52(C)(1),
occupying assigned spaces shall not be considered as these required outlets.
 Exception: In dwelling units designed to be accessible to persons with disabilities,
receptacles shall be permitted to be installed not more than 300 mm (12 inches) below the
countertop or work surface. Receptacles installed below a countertop or work surface shall
not be located where the countertop or work surface extends more than 150 mm (6 inches)
beyond its support or base."
(9) NEC, Section 210.12, is deleted.
(10) NEC, Section 210.65, is deleted.
(11) NEC, Section 215.18, is deleted.
(12) NEC, Section 225.42 is deleted.
(13) NEC, Section 230.67, is deleted.
(14) NEC, Section 230.71, is deleted and replaced with the following:
"230.71 Maximum Number of Disconnects.
(A) General. The service disconnecting means for each service permitted by 230.2, or for
each set of service-entrance conductors permitted by 230.40, Exception No. 1, 3, 4, or 5 shall
consist of not more than six switches or sets of circuit breakers, or a combination of not more
than six switches and sets of circuit breakers, mounted in a single enclosure, in a group of
separate enclosures, or in or on a switchboard or in switchgear. There shall be not more than
six sets of disconnects per service grouped in any one location. For the purpose of this section,
disconnecting means installed as part of listed equipment and used solely for the following shall
not be considered a service disconnecting means:
(1) Power monitoring equipment;
(2) Surge-protective device(s);
(3) Control circuit of the ground-fault protection system; or
(4) Power-operable service disconnecting.
(B) Single-Pole Units. Two or three single-pole switches or breakers, capable of individual
operation, shall be permitted on multiwire circuits, one pole for each ungrounded conductor, as
one multipole disconnect, provided they are equipped with identified handle ties or a master
handle to disconnect all conductors of the service with no more than six operations of the hand.
(C) Beginning on July 1, 2027, Section 230.71(B) is no longer in effect."
(15) NEC, Section 314.27(C), is deleted and replaced with the following: "314.27(C) Boxes at
Ceiling-Suspended (Paddle) Fan Outlets. Outlet boxes or outlet box systems used as the
sole support of a ceiling-suspended (paddle) fan shall be listed, shall be marked by their
manufacturer as suitable for this purpose, and shall not support ceiling-suspended (paddle)
fans that weigh more than 32 kg (70 lb). For outlet boxes or outlet box systems designed
to support ceiling-suspended (paddle) fans that weigh more than 16 kg (35 lb), the required
marking shall include the maximum weight to be supported."
(16) In NEC, Section 334.24, the last sentence is deleted and replaced with the following:
"For flat cables, the minor diameter dimension of the cable shall be used to determine the
bending radius when bending on the flat side of the cable. For all other bends, the major
diameter dimension shall be used."
(17) In NEC, Section 334.80, the second paragraph is deleted.
(18) In NEC, Section 338.24, the last sentence is deleted and replaced with the following:

"For flat cables, the minor diameter dimension of the cable shall be used to determine the
bending radius when bending on the flat side of the cable. For all other bends, the major
diameter dimension shall be used."
(19) In NEC, Section 406.9(B) number (2), the following words are deleted:
"be listed weather-resistant type, and installation shall".
(20) NEC, Section 700.3(A) is deleted and replaced with the following:
"700.3(A) Conductor Witness Test.
The authority having jurisdiction shall conduct or witness a test of the complete system upon
installation and periodically afterward."